Interpretation #7928

Published May 02, 2017

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
7
Section
704.1 Means of Egress
Topic
EERO replacement windows

Question

Is it the intent of 704.1 Exception, to allow a nonconforming
bedroom egress window to be reduced an additional
5-percent with a replacement window.

Answer Published 05/02/2017 at 8:23 AM

The Existing Buildings volume, section 403.1 tells us that alterations shall be such that the existing building or structure is no less conforming. The 5% reduction was put in place to factor in stronger windows and is based on discussions with the window manufacturers during the code change cycle. This reduction applies to an opening which complied at the time it was originally built. Further reducing a noncompliant opening would make the building less conforming.

Commentary

An existing window can be reduced by 5% with a replacement unit whether the existing window meets the emergency escape and rescue opening size requirements or not. The exception does not specify any differences between conforming and nonconforming openings, but applies to all replacement windows and doors.