Interpretation #7923

Published June 05, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
10
Section
1008.1.2
Topic
Purpose of side hinged door

Question

Is it the intent of having a pivoted or side-hinged swinging
type only restricted to independent door systems or can a
hybrid horizontal sliding door with a pivoted system
(breakout) be used as a means of egress?

Answer Published 06/05/2017 at 11:50 AM

Code allows for alternatives. You need to continue reading through all of 1008.1.2. Exception 6 allows for horizontal sliding doors. These doors must then meet the requirements found in Section 1008.1.4.3. It also allows in exception 7 power operated doors meeting the requirements of Section 1008.1.4.2.
As a side note, make sure that any specific requirements found in Sections 407 and 449 are also met.

Commentary

None