Interpretation #7920

Published October 10, 2017

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
461.1
Topic
Fire sprinkler design criteria

Question

Is it the intent of Section 461.1to eliminate the use NFPA 13R fire protection systems in transient lodging facilities even when the building meets the listed criteria of Chapter 5 that would qualify it to be designed with such a system? Conversely can an NFPA 13R system be used in a transient lodging facility with interior corridors but meets all applicable criteria of Chapter 5 of the F.B.C. 2014 addition?

Answer Published 10/10/2017 at 10:30 AM

Yes

Commentary

None