Interpretation #7907

Published May 02, 2017

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
16
Section
M1601.1
Topic
Duct Construction

Question

Is it the intent of M1601.1 to require Florida Licensed Professional Engineers to use ACCA Manual D to size ductwork in residences, or may a PE use standard procedures as outlined by ASHRAE and typically used in commercial applications for sizing ductwork?

Answer Published 05/02/2017 at 8:30 AM

No, the Section cited specifically states "or other approved methods". There is no problem with accepting a design by ASHRAE, with careful evaluation a local authority could accept a manufacturer's program, but it would be a local determination.. If the jurisdiction where the referenced project is not accepting the manufacturer's program, that is fully within their authority.

Commentary

None