Interpretation #7907
Published May 02, 2017
Original Request
- Code Version
- 2014
- Code
- RESIDENT
- Code Description
- Chapter
- 16
- Section
- M1601.1
- Topic
- Duct Construction
Question
Is it the intent of M1601.1 to require Florida Licensed Professional Engineers to use ACCA Manual D to size ductwork in residences, or may a PE use standard procedures as outlined by ASHRAE and typically used in commercial applications for sizing ductwork?
Answer Published 05/02/2017 at 8:30 AM
No, the Section cited specifically states "or other approved methods". There is no problem with accepting a design by ASHRAE, with careful evaluation a local authority could accept a manufacturer's program, but it would be a local determination.. If the jurisdiction where the referenced project is not accepting the manufacturer's program, that is fully within their authority.
Commentary
None