Interpretation #7871

Published November 22, 2016

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
3
Section
318.7 exception 4
Topic
FOOTINGS

Question

Is it the intent of R318.7 exception 4 to only allow chemical soil treatment and not registered wood or bait termiticide in the area prescribed?

Answer Published 11/22/2016 at 11:28 AM

No. Please see the attached commentary

Commentary

While it is true there may be situations where the mix is permissible such as hotel residential areas vs. assembly or commercial areas, in this case the increase in height is based on the entire building being sprinklered per the required NFPA system. In the case of the I-1 Occupancy, the height increase is based on a NFPA 13 system. The reference to Section 903.3.1.1 is not a "generic" reference, but specifically requires a NFPA 13 system. If a 13R system is permitted, the reference would be to 903.3.1.2. In addition, the use of a 13R system is limited to four stories. This building is 5 stories. The answer is to provide a NFPA 13 system throughout the building.