Interpretation #7864

Published November 14, 2016

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
5
Section
501.3.2
Topic

Question

Is it the intent of the code to allow a flapper/damper and
screen protection for a residential wall cap (mechanical
Ventilation)

Answer Published 11/14/2016 at 9:03 AM

The answer is "PROBABLY." The request does not state whether
the exhaust is bathroom, kitchen, or clothes dryer. The
referenced section says nothing about flappers or dampers, It
addresses screens. Section 504.4 mandates a backdraft
damper and prohibits screens at the termination.

Commentary

While 501.3.2 refers to a commercial application, residential occupancies not covered by the residential volume fall within this category. If the issue relates to a One or Two Family Dwelling, the wall cap duct termination would be section M1506.2 of the residential code. This section then sends you to 303.6 Outside Opening Protection: ... shall be protected with screens louvers or grilles ...opening shall be protected against local weather conditions... based on this, the answer is yes if the flapper purpose is weather protection for that residential application. Note: No screen allowed in a dryer application