Interpretation #7861

Published November 09, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1710.5.1
Topic

Question

Is it the intent of this section to require labels that show the
series number, wind pressures, etc. even on exterior steel
doors?

Answer Published 11/09/2016 at 7:58 AM

Yes, this section applies to all exterior windows and doors,
regardless of the material used to construct them.

See 1710.5.1 for specifics on permanent and temporary label
requirements.

Commentary

Some door assemblies are manufactured by different companies and as such there is not a single manufacturer to issue a label. These situations are usually handled via a Florida Approval or an NOA that lays out the requirements. Organizations such as WDMA and AAMA provide individual pieces and parts such as hinges, handles, operators and so on that are individually listed and may be put together to fit a specific need. In this case, much like a fire rating assembly, a product approval, NOA or other acceptable engineering document needs to be presented for acceptance.