Interpretation #7850

Published November 03, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
706.2
Topic
Lateral bracing for fire resistance

Question

If the lateral bracing members and attachment components of a firewall were all designed to act in conjunction with the firewall as a single fire-rated assembly for at least the duration of the fire/fire-rating as required by code, would this meet the intent for Section 706 of the code?

Answer Published 11/03/2016 at 9:50 AM

That would depend on what supported the lateral bracing
members and attachment components. If the lateral brace was
attached to an element other than the fire wall and the other
element collapsed causing failure of the brace, no.

Commentary

None