Interpretation #7848

Published November 03, 2016

Download Final PDF

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
601.5
Topic
Application of "haitable"

Question

Is it the intent of section 601.5 to apply to all occupiable spaces or does the language of exception #3 stating "Habitable only shall be required to met these requirements..." mean that all of 601.5 only applies to habitable rooms?

Answer Published 11/03/2016 at 9:49 AM

No, the intent is not to apply balanced air requirements to
all "occupiable" spaces. The provision applies to "habitable
rooms" only.

Commentary

As the requester points out, the wording of Exception #3 is remarkably poor. This being the case, it is unlikely that the author intended for any reader to read Exception #3 several times between the lines in an effort to interpret/extract intent or meaning. Perhaps there should have been 4 Exceptions. The first part of Exception #3 exempts bathrooms, closets, storage rooms and laundry rooms. The last part of Exception #3 should have become Exception #4 �except that all supply air into the master suite shall be included�. (Balancing the return and supply air into the master suite became a concern for the Technical Advisory Committee due to the large size of some master suites with his and hers closets, dressing areas, bath area, shower, toilet rooms, etc.)