Interpretation #7839

Published September 30, 2016

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
M1502.4.2
Topic
Dryer vent

Question

Is it the intent of this section that all dryer venting shall have screws or similar fasteners to be considered mechanically fastened?

Answer Published 09/30/2016 at 1:56 PM

Yes to mechanical fastening. The code clearly states: "... and
shall be mechanically fastened". The codes does not. however,
specify the use of screws or rivets. The Section references
Section M1604.41 and other methods of mechanical fastening are
mentioned there, such as crimping. The allowable fastening
methods may rely on the material and in some cases the shape
of the duct. The code does stipulate that screws or similar
fasteners shall not protrude more than 1/8-inch into the
inside of the duct.

Commentary

None