Interpretation #7837

Published September 30, 2016

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
601.5
Topic
Dampers in return grills for T&B

Question

Is it the intent of 601.50 to disallow the use of dampers in return grills for the purpose of test and balance?

Answer Published 09/30/2016 at 1:55 PM

No

Commentary

FBC Mechanical 601.5 requires only balanced return air and constrains the design to ensure that pressure differentials across closed doors are no greater than 0.01 inches of water column. If the design includes return grilles that are properly sized, with dampers, so as to limit the pressure differential to the Code-mandated 0.01 inches of water column, dampers are, of course, allowed.