Interpretation #7836

Published September 28, 2016

Original Request

Code Version
2014
Code
PLUMBING
Code Description
Chapter
Section
301.3
Topic
Water fountain drains

Question

Is it the intent of section 301.3 to include water fountains that are not located at a building structure (such as in a parks or at youth sports field functions) to be tied into sanitary drainage systems?

Answer Published 09/28/2016 at 9:46 PM

The answer to the question is, "NO."
301.3 addresses only liquid waste or sewage. It's a stretch
to conclude that drinking fountain drains contain, "animal
or vegetable matter in suspension." Further, FBC - Plumbing
701.2 refers only to buildings. Outdoor showers with no
piped drains at all are routinely installed at poolside and
near beaches. Some of these are even fitted with
drinking bubblers. In a park or ballfield installation,
keeping rain water out of any drinking fountain's sanitary
drain would be an additional challenge. The only problem
with the desired approach is that there is no definitive
statement in the Code stating that the proposed installation
can be built as described. The requester should present the
proposal to the authority having jurisdiction for approval
under FBC 2014 104.11, Alternative materials, design and
methods of construction and equipment.

Commentary

Historically, drinking fountains in sports and recreation parks/facilities have been granted an exception to section 301.3 requiring connection to a sanitary system by the AHJ. The exception is based on the difficulty and expense of extending a sanitary line to the location when there is no adjacent structure with a plumbing system. Examples would be bubblers at baseball dugouts and random placement on golf courses or parks. Technically applying this code section based on the strict definition of liquid waste might be legally defended, however, the potential for deleterious discharge (the intention of the code section is to prevent such) to grade by the use of a drinking fountain would be extremely remote and thus the use of the common-sense exception. The point of discharge would be the only concern as to simply allow the drinking fountain to discharge to grade as opposed to a french style drain could possibly create a nuisance situation if the discharge did not perk into the soil at a sufficient rate. While technically the answer may be yes, most agree that the FBC is not comprehensive enough to rise to a one size fits all in some areas. The purpose of Code Officials is to add an element of discretion in cases such as this.