Interpretation #7833

Published September 28, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1015
Topic
Travel distance calculation

Question

We have an R2 occupancy (condominium), 7 floors mid rise, linear unit arrangement with open air egress balcony on rear with elevator in middle and (2) 2-hr fire rated enclosed stair towers at each end of an egress balcony. Separation of the stairs is limited to 1/3 (sprinkled) of the diagonal of building or area served. Is the area served just the egress balcony since you have to walk out your fire rated front door to enter the exit access or is it 1/3 of the entire building diagonal?

Answer Published 09/28/2016 at 9:44 PM

Since this is an exception to the 1/2 of the diagonal apart
equal to not less than one-half of the length of the maximum
overall diagonal dimension of the building or area to be
served (1015.2.1) It would be the ENTIRE BUILDING DIAGONAL
as best case scenario. The area served would relate to the
location of the exit doors in the units proper.

Commentary

The diagonal is the length of the maximum overall diagonal dimension of the building. The area served provision would apply If two exits or exit access doors were required from one of the units or other room within the building.