Interpretation #7831

Published September 23, 2016

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
E3901.7
Topic
Outdoor receptacle

Question

Is it the intent of this section to require a new receptacle be installed on an existing building exterior wall adjacent to a new "open patio area" created by paver blocks at grade? There already exists two receptacles on this exterior wall within a screened area that has a screen door adjacent to the pavers.

Answer Published 09/23/2016 at 8:42 AM

No, the ones inside the screen area would suffice
for the required one, if this area was ever
enclosed then an outlet would be required.