Interpretation #7801

Published August 05, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
903.2.8
Topic
Fire Sprinkler for Community Residential Home

Question

Is it the intent of this section to require a fire sprinkler for a Community Residential Home with five or fewer residents (as defined in Chapter 419 F.S.)?

Answer Published 08/05/2016 at 11:26 AM

We are not able to interpret statutes outside the scope of
the building code but.... that statute states "(2) Homes of
six or fewer residents which otherwise meet the definition
of a community residential home shall be deemed a
single-family unit and a noncommercial, residential use for
the purpose of local laws and ordinances." The building code
is not a local law or ordinance, it is adopted as a rule
under the Florida Administrative Code guided by Florida
Statute 553 and therefore, while we cannot offer legal
advice, it appears this statute may not apply.

Commentary

None