Interpretation #7799

Published July 21, 2016

Download Final PDF

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1018.1 and Table 1018.1
Topic
Rating of corridors

Question

Is it the intent of Section 1018.1, Exception 4, to allow single exit suites with less than 30 occupants within a larger building with more than 30 total occupants to have corridors within the single exit suite that are not required to be 1 hour rated?

Answer Published 07/21/2016 at 3:42 PM

The answer is probably no. The door from the suite is not an
exit, but an exit access doorway per 1015.1 and Table 1015.1
as referenced in 1018.1 Exception 4, provided the occupant
load is less than 49 per Table 1015.1.

Commentary

Additional information may be needed or not provided. For example, there is a common path requirement that also must be applied (1014.3). Is the 75' from the furthest point inside the suites to the exit door leading to the rated corridor? (the point at which there are 2 remote exits?)