Interpretation #7790

Published July 18, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
2508
Topic
Soffit board using 24" centers

Question

Is it the intent of the FBC, as it references GA-216 in Table 2508.1 (GA-216 specifically prohibits the use of 1/2" Soffit Board to be installed to trusses 24"OC), to prohibit the use of 1/2" Soffit Board on 24" OC in exterior installations? Could this be done as described if designed by a Florida Registered Engineer?

Answer Published 07/18/2016 at 10:31 AM

"Gypsum Board shall not be used where there will be direct
exposure to water or continuous high humidity." Per 2508.2.
An alternate is to use gypsum sheathing installed per ASTM
C 1280. So the answer is "yes" it is prohibited.

Commentary

It is the intent to prohibit Gypsum Board outdoors as is regulated by GA-216. 2508.2 Soffit Board is usually a form of Gypsum Sheathing. Gypsum Sheathing is installed per ASTM C 1280 and the manufacturer's approved instructions. Maximum framing spacing regardless of wind load must comply with manufacturer's installation instructions. If a Product Approval or ICC Evaluation Report is not available regarding wind loads, an engineer can design the Assembly that includes the Soffit Board.