Interpretation #7787
Published June 03, 2016
Original Request
- Code Version
- 2014
- Code
- BUILDING
- Code Description
- Chapter
- Section
- 907.2.11.2
- Topic
- Smoke alarm replacement
Question
As part of the company's service to customers we offer to check smoke alarms with canned smoke. If I find an older, hard wired alarm that no longer functions properly can said alarm be replaced with a new BATTERY OPERATED alarm as long as the battery in said alarm is of the 10 year type as now required? Or must the replacement alarm also be hard wired as well as have a 10 year battery back up? Thank you.
Answer Published 06/03/2016 at 2:47 PM
No. Please see the attached commentary
Commentary
907.2.11.4 states that hard wired alarms are required for
new construction. Lacking any more information, if the
alarm was hard-wired to begin with, it must have been
required at the time is was installed, and must be replaced
in-like-kind.
FBC,Existing Building section: SECTION 603 FIRE PROTECTION
603.1 General. Repairs shall be done in a manner that
maintains the level of fire protection provided.