Interpretation #7772

Published May 25, 2016

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
Section
804.1.1
Topic
Reduction of stairwell rating with sprinklers

Question

Is it the intent of FBC-Existing 804.1.1 to not allow a reduction in the fire-resistance rating of the corridor unless stairwell landings serving the floor and the intermediate landings immediately below have sprinkler coverage even though the noncombustible stairwell already complies with NFPA 13 with sprinklers only at the top of shaft and at the bottom landing of stairwells?

Answer Published 05/25/2016 at 3:00 PM

Yes, 804.1.1 is clear, in existing buildings going thru
level 2 alterations, no reduction in fire resistance is
allowed in corridors if sprinkler coverage for the landings
is not provided.

Commentary

The requestor's comment regarding the existing code being more stringent than the new code is not a glitch. You need to factor in that the existing code governs buildings built to many different code versions and fire protection is a complete package which includes smoke/fire detection, annunciation, fire protection ratings, fire extinguishing and notifications. Existing buildings may not have all the latest features of fire protection which allow the safe reduction of the corridor rating.