Interpretation #7769

Published May 25, 2016

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
Section
606.2
Topic
Reroofing requirements

Question

Is it the intent of the removal of the reference to the Alteration Level 1 Reroofing Section (FBC 2014 Section 708) within section 606.2 (when compared to FBC 2010 Repair Section 506.2), to remove the 25% threshold requirement for full roof replacement if we are performing a repair? For instance, if the work classification per Chp 5 is a Repair, can we repair 40% of the roof without referring to Section 708 and/or FBC Building Chapter 15?

Answer Published 05/25/2016 at 2:59 PM

No. A recent Dec Statement was issued on this question.

Commentary

Please refer to Declaratory (DEC) statement 2015-135 which may found on the Florida Building Commission website. The specific location is: http://www.floridabuilding.org/Upload/FBC/CodeID_7288_b11d_DS%202015-135%20-%20Davies%20of%20Bracken%20Engineering.pdf