Interpretation #7743

Published March 23, 2016

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
1609.1.2
Topic
Wind borne debris coverings

Question

Is it the intent of Section 1609.1., reference exception in paragraph, "to allow" approved window coverings (wind borne debris zone) on residential new construction with a mean roof height below 45' feet?

Answer Published 03/23/2016 at 8:09 AM

The mean roof height limitation and the number of stories
limitations apply solely to wood structural panels. All
impact resistant coverings or systems are required to have
either a Florida Approval or a local approval per Ch.
553.842 or Ch 553.8425, F.S. Being accessible from a deck or
other walking surface is irrelevant.

Commentary

In the wind borne debris region, all openings within 30 feet of grade are required to be protected from large missile impact. All openings above 30 feet are required to be protected from small missile impact. ALL protection products are required to be tested to conform to the standards listed. A Florida Product Approval is an optional method of proving conformance. If it is an R-3 or R-4 residential structure, Exception 1 for wood structural panels can be utilized.