Interpretation #7740

Published March 28, 2016

Original Request

Code Version
2001
Code
PLUMBING
Code Description
Plumbing
Chapter
7
Section
702.3, 703
Topic
29

Question

Is it the intent of section 702.3 and 703 to require Type 'K' or 'L' copper piping for sanitary force main piping?

Answer Published 03/28/2016 at 11:13 AM

Based on the 2001 Florida Code, what is described is
actually part of the building drain and not the sewer which
are the sections referenced in the question. In order to
answer the question as described, not the sections cited,
please see section 702.1 of the 2001 Florida Building Code -
Plumbing. This sections refers to table 702.1 for the
appropriate materials.

Commentary

If work is being performed in an existing structure, please refer to the Florida Building Code - Existing Buildings volume for the requirements for work to be performed. This will determine what work is permitted to comply with the code in effect at the time of construction or the current edition of the Florida Building Code.