Interpretation #7732

Published February 29, 2016

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1018.1
Topic
Reduced rating with sprinklers

Question

Is it the intent of 1018.1 and Table 1018.1 to eliminate the requirement for a fire resistive rating as well as a smoke resistant requirement for an "E" occupancy that has a sprinkler system?

Answer Published 02/29/2016 at 9:25 AM

Yes, Depending on the situation, other Codes, specifically
NFPA 101, 7.1.3.1, may require a 1-hour fire rated separation.

The most restrictive requirement will apply.

Commentary

1018.1 under certain circumstances relieves the fire resistant rating for a corridor in an E occupancy.