Interpretation #7730

Published February 23, 2016

Download Final PDF

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
303.1.1
Topic
Restaurant occupant load

Question

Is it the intent of the FBC 2015 5TH Edition(2014)Building Section 303.1.1 to utilize an occupant load factor of 100 gross/person (Business) to determine the occupancy load of a restaurants (A-2) dining and kitchen spaces instead of 15 net/person (dining area) and 200 gross/person(kitchen)?

Answer Published 02/23/2016 at 3:16 PM

No. If you read the occupant load factor in Table 1004.1.2,
it lists "Function of Space" not "occupancy". Please see the
attached commentary for additional information.

Commentary

While the occupancy classification may be Business when the OL is less than 50, the use or function is still A-2 for the determination of egress capacity, etc. The net areas of 7, 5, and 15 sq. ft./person or the number of fixed seats and the 200 gross sq. ft. for the kitchen area are used to determine whether the occupant load is below the 50 persons to allow classification as Group B. Please note the heading of column 1 of Table 1004.2 is "Function of Space"; not occupancy classification of space.