Interpretation #7714

Published February 01, 2016

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
403.3
Topic
Outdoor air in a commercial kitchen

Question

Is it the intent of Table 403.3 FBC14 Mechanical to not require outdoor air for occupants in a commercial kitchen.

Answer Published 02/01/2016 at 11:02 AM

No. Please see the attached commentary

Commentary

Since exhaust is required, the air that is exhausted must be replaced with outdoor air, or air (a subset of which is outside air) may be transferred from adjacent spaces. This is the mechanism by which outside air is introduced. Generally, commercial kitchen exhaust quantities are so great, that more than adequate ventilation is made available to the occupants of the kitchen.