Interpretation #7704
Published January 13, 2016
Original Request
- Code Version
- 2004
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 16
- Section
- 1604.3
- Topic
- Deflection of stucco wall
Question
Is it the intent of 2004 Florida Building Code that the structural wall framing assembly behind stucco be designed to a wind performance criteria of l/240 deflection?
Answer Published 01/13/2016 at 8:46 AM
Yes
Commentary
The ASTM also requires the fasteners for the wire to attach
to the studs with the studs spaced no more than 16 inches
o.c. This spacing often solves the deflection issue. We
would also point out the table has been expanded in the 5th
Edition and specifically identifies plaster or stucco with a
deflection limit of l/360.