Interpretation #7704

Published January 13, 2016

Original Request

Code Version
2004
Code
BUILDING
Code Description
Building
Chapter
16
Section
1604.3
Topic
Deflection of stucco wall

Question

Is it the intent of 2004 Florida Building Code that the structural wall framing assembly behind stucco be designed to a wind performance criteria of l/240 deflection?

Answer Published 01/13/2016 at 8:46 AM

Yes

Commentary

The ASTM also requires the fasteners for the wire to attach to the studs with the studs spaced no more than 16 inches o.c. This spacing often solves the deflection issue. We would also point out the table has been expanded in the 5th Edition and specifically identifies plaster or stucco with a deflection limit of l/360.