Interpretation #7702

Published December 22, 2015

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
202 - Exterior Wall
Topic
Exterior wall

Question

A parking garage has a fire wall immediately adjacent to a

restaurant kitchen; the kitchen has its own non-rated wall

adjacent to the fire wall. Are either of the walls considered an exterior wall per FBC?

Answer Published 12/22/2015 at 10:11 AM

They are exterior walls only if enclosing the building from
the outdoors.

Commentary

If there is a lot line between the garage and kitchen the opening between them is prohibited - 706.1.1. Based on the comment to the question and since the kitchen has its own wall, it does not sound as though the walls are on a lot line or that the fire wall is used or adapted for joint service between buildings.If that is the case, the prohibition against openings of Section 706.1.1 does not apply. If the kitchen has fuel fired equipment 406.4.7 applies.