Interpretation #7699

Published December 22, 2015

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
404.1.2
Topic
Activation of CO garage ventilation

Question

Is it the intent of the 5th Edition code to eliminate or change the minimum threshold of 25 ppm CO that would

automatically activate a garage ventilation system as

mandated by prior codes? If so, what would be an

appropriate activation threshold of the CO detection devices?

Is the intent for the activation level to be at the discretion the Engineer of Record and/or the Building Official?

Answer Published 12/22/2015 at 9:42 AM

The threshold is not in Section 404.1.2.

Commentary

The selected product needs to be installed in accordance with the manufacturer's recommendations. If the manufacturer (and the product listing) of a detector contemplates its use as an activation device for a garage ventilation system, and if the manufacturer's instructions are followed, the installation would be in compliance with 404.1.2.