Interpretation #7693

Published December 22, 2015

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
M1503
Topic
Range exhaust requirements

Question

Is it the intent of this section to require exhaust thru the roof

for a gas fired range? What if the range installed is electric

powered, does it still require exterior termination?

Answer Published 12/22/2015 at 9:40 AM

No. The requirement is for the duct to terminate to the
exterior, however, it is not required to penetrate the roof,
it could be a sidewall.

Commentary

An exhaust hood ducted to the outdoors is not required as long as: Where installed in accordance with the manufacturer�s installation instructions, and where mechanical or natural ventilation is otherwise provided, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.