Interpretation #7689

Published December 15, 2015

Original Request

Code Version
2014
Code
PLUMBING
Code Description
Chapter
Section
403
Topic
Urinals and potty parity

Question

Is it the intent of 403.1.3 Potty Parity to prevent providing fixtures in excess of what table 403.1 requires to a men's toilet room, without providing additional fixtures at a 3:2 ratio in the women's toilet? A joint-use high school/community theater on a high school campus has been designed in compliance with Table 403.1 and 403.1.1 and the owner has requested an additional five (5) urinals for a total of 7 urinals and 2 water closets in the restroom. Will this also violate the 50% limit requirement of 419.2 for urinal substitution of water closets?

Answer Published 12/15/2015 at 3:52 AM

Yes. While it would be nice to say this is based solely on
the "required", the code states the number of fixtures

"provided" not the number of fixtures "required". After all,

the reason the potty parity law was enacted was because of

the long waits for the facilities for women at large venues

like stadiums, concert halls and the like.

Commentary

Statutory excerpt that creates the Code requirement: ... "In assembly occupancies, restrooms which are open to the public must have a ratio of 3:2 water closets provided for women as the combined total of water closets and urinals provided for men," ...