Interpretation #7685
Published November 06, 2015
Original Request
- Code Version
- 2014
- Code
- BUILDING
- Code Description
- Chapter
- Section
- 1029.1
- Topic
- EERO for 4 story
Question
Is it the intent of section 1029.1 to require ALL R-2 occupancies to be provided with at least one exterior emergency escape and rescue opening for sleeping rooms below the fourth story above grade plane other than the 4 exceptions as noted?
Answer Published 11/06/2015 at 1:30 PM
Yes, The code requires EERO for all sleeping area for floors
below the 4th floor for R-2 occupancies.
below the 4th floor for R-2 occupancies.
Commentary
The Florida Fire Prevention Code (FFPC) at Section 30.2.1.2
also requires a secondary means of escape. The FFPC allows
other than windows as a means of escape, but windows are an
acceptable alternate.