Interpretation #7685

Published November 06, 2015

Download Final PDF

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
1029.1
Topic
EERO for 4 story

Question

Is it the intent of section 1029.1 to require ALL R-2 occupancies to be provided with at least one exterior emergency escape and rescue opening for sleeping rooms below the fourth story above grade plane other than the 4 exceptions as noted?

Answer Published 11/06/2015 at 1:30 PM

Yes, The code requires EERO for all sleeping area for floors
below the 4th floor for R-2 occupancies.

Commentary

The Florida Fire Prevention Code (FFPC) at Section 30.2.1.2 also requires a secondary means of escape. The FFPC allows other than windows as a means of escape, but windows are an acceptable alternate.