Interpretation #7680

Published November 06, 2015

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
2506
Topic
Steel studs in fire partition

Question

Are steel track and studs complying with ASTM C645 acceptable to use in fire rated partitions. Example Clark Dietrich Pro Stud 15mil which appears to be thinner than allowed in section 2517.5.1.

Answer Published 11/06/2015 at 1:10 PM

The studs and tracks must be part of a tested
assembly or equivalent to the studs and tracks
used in a tested assembly. The tested assembly
referred to is a fire tested assembly per ASTM E
119.

Commentary

None