Interpretation #7672

Published November 03, 2015

Download Final PDF

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
2709
Topic
Waterproffing of showers

Question

Is it the intent of 2709.2 (lining required) to require a water proofing method on "all" showers, recessed or not?

Answer Published 11/03/2015 at 10:36 AM

Yes, the exception for recessed showers was
removed. All showers are now required to
have pans or liners.

Commentary

The intent was to not require linings only when prefabricated watertight wall and receptor units are installed. "Built-up" is hyphenated to represent site fabricated. Otherwise, it would be "built up", no hyphen. Just as a built-up roof only means an assembly of multiple layers, not a specific height. Recessing the slab does not prevent water from soaking through walls. Recessing the slab does not prevent cracks in the slab from allowing water to run between the vapor barrier and slab causing problems throughout the structure.