Interpretation #7660

Published October 16, 2015

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1006.2.3.2
Topic
Disconnection of egress lighting circuits

Question

Is it the intent of the requirement "opening of a circuit breaker or fuse" to be applied to all branch circuits serving egress lighting facilities or only to the branch circuits serving normal lighting facilities?

Answer Published 10/16/2015 at 2:48 PM

It is not the intent of these sections to require battery
backup on everything. The last word of section 1006.2.3.2 is
"facilities". This means the lighting system, not the
individual branch circuits.

This is much cleaner in the 5th Edition. This question was
previously answered under interpretation number 6925. While
that particular question was related to the 2007 edition of
the Florida Building Code, the answer remains the same.
Please see that interpretation for a complete commentary on
the requirements.

Commentary

Refer to interpretation #6925