Interpretation #7659
Published October 16, 2015
Original Request
- Code Version
- 2014
- Code
- BUILDING
- Code Description
- Chapter
- Section
- 420
- Topic
- Group home occupancy
Question
Two questions. First, does a 6 bed group home for kids count as R-3 or R-4? Second question, relating to section 420, if the home for 6 children has a 13D sprinkler system and full fire alarm system, does it need fire rated walls and floors?
Answer Published 10/16/2015 at 2:47 PM
Question 1: R-4, assuming the group home is as defined by
the code.
Question 2: Section 420 is not applicable because the
occupancy class is R-4.
the code.
Question 2: Section 420 is not applicable because the
occupancy class is R-4.
Commentary
Look at sections 310.5 and 310.6 to determine which
Occupancy Code applies to a specific application when
applying the Building Code. If there is a question, a
discussion should be had with the appropriate authority
having jurisdiction.