Interpretation #7656
Published October 09, 2015
Original Request
- Code Version
- 2014
- Code
- RESIDENT
- Code Description
- Chapter
- Section
- R806
- Topic
- Residential attic ventilation
Question
Is it the intent of Section R806.2 (Residential), to reflect the same exceptions for attic ventilation as listed in Section 1203.2 (Building)?
Answer Published 10/09/2015 at 12:42 PM
No. It is not the intent is for the exceptions in the two
code volumes to be the same. Please see the attached
commentary for an explanation and possible actions.
code volumes to be the same. Please see the attached
commentary for an explanation and possible actions.
Commentary
Perhaps there should not be a difference. Our opinion, hence
a commentary, is Section R806.2 seems to more accurately
describe the intent. Since we are in a code development
cycle, a coordination of these two sections appears to be in
order. The following is offered as an explanation of the
intent of these two sections. Both sections contemplate
ventilation at the eaves alone with a net free ventilation
area of 1/150 (square feet) or a combination of eave and
ridge ventilation where the net free ventilation area may be
reduced to 1/300 (sq ft). Proper attic ventilation must
ensure balanced venting. Balance is achieved when no more
than 50 percent of the ventilation installed is provided in
the upper portion of the attic and the remainder of
ventilation is provided at eaves or cornices. The key to
balanced ventilation is to make sure air moves into the
attic at the eaves and out through the ridge vents or other
vents in the upper portion of the attic. The object is to
make certain air enters the attic at the eaves and exits
through the ridge vents. However, if more ventilation is
provided at the ridge or upper portion of the attic, the
flow of ventilation will be reversed. This causes a lack of
efficiency as air entering at the ridge encounters rising
hot air interfering with the removal of hot humid air from
the attic.
Additionally, the reversal of attic air flow can be expected
to draw in precipitation at the ridge. Section 1203.2
indicates as much as not less than 50 and no more than 80
percent of the �required ventilation� may be located in the
upper portion of the attic. However, the commentary for this
section stresses that the ventilation at the eave and upper
portion of the attic must be balanced.
Having said that, in some townhome buildings the interior
units with only front or rear eaves are limited with the
eave ventilation. Therefore, it may be difficult to meet the
max of 50% in the upper portion of the roof. The Building
Official may allow an alternate method like a power
ventilator to meet the intent of the code.