Interpretation #7649

Published October 06, 2015

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
309.1
Topic
Separating a stock room from retail

Question

Is it the intent of the FBC 309.1 to create a separate Storage Occupancy separation for the Stock Room to a retail store?

Answer Published 10/06/2015 at 9:58 AM

No. The change regarding accessibility by the public was to
account for increasingly popular venues such as Sam's Club,
Costco, etc. where the sales area and storage area are the
same.
The code also permits accessory occupancies ancillary to
the main occupancy to be classified the same as the main
occupancy, provided area limitations are met. Finally,
Table 508.4 does not require rated separation between
Groups M and S-1. tire storage is classified as S-1. We
cannot locate the section referenced in the FFPC

Commentary

None