Interpretation #7634

Published September 24, 2015

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
303
Topic
Classification of an exercise room

Question

Is it the intent of the code to classify a fitness/exercise studio as assembly? or business? if it is less than 50 occupants? What about table 1004.1.2 Exercise room? NFPA does not have the option of exercise room.

Answer Published 09/24/2015 at 4:00 PM

Yes, recreation is A-3 - 303.4. If less than 50 then
Business - 303.1.1.

NFPA 101, Table 7.3.1.2 - Exercise room with or without
equipment. The Appendix at A3.3.188.2 has an expanded list
including Gymnasium.

Commentary

Even if classified as A-3 (occupant load of 50 or more), the occupant load factor of Exercise rooms in Table 1004.1.2 would apply as it is based on the function of the space as opposed to the occupancy classification. If using the occupant load factor of 50 sq. ft. gross results in an occupant load of 50 or more, panic or fire exit hardware is required.