Interpretation #7630

Published September 21, 2015

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
Section
101.2 Exception.
Topic
Application of existing volume to hospitals

Question

Is it the intent of Section 101.2 (and FBC Building 449.1.3) to exempt existing private hospitals that are state licensed to comply with FBC Existing Building?

Answer Published 09/21/2015 at 2:05 PM

Yes, the intent is to exempt such buildings from the Florida
Building Code-Existing Building. However, the provisions in
Chapter 4 for public educational and state licensed
facilities essentially say that all remodeling, alterations,
renovations, repairs, additions, and change of occupancy
have to meet the code requirements for new construction.
The separation by a fire wall would create two separate
buildings.

Commentary

The Building Code fully addresses not permitting a new adjacent building that would impede upon the open frontage area required for an existing building. The permit applicant needs to provide documentation of how the existing building will have adequate firefighting capabilities equivalent to that available with the previous open space. FBC-B 104.11 provides for alternative means of compliance. From the Comment by the requester, the building is already non-conforming. The alternatives are to deny the permit for the addition, require life safety features above what is required by the code as an alternative method, or continue to allow the non-conformance. This situation is not really addressed by the code and is wholly a local jurisdiction decision.