Interpretation #7627

Published September 18, 2015

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
307.2.3 #4
Topic
Location of overflow cutoff

Question

Is it the intent of the code to allow a overflow cutoff switch that is ul listed and tested to ul 508 in Either the secondary outlet of the units drain pan OR in the primary drain line.

Answer Published 09/18/2015 at 4:16 PM

Yes. Section 307.2.3, 4. states,"...shall be installed in
the primary drain line, the overflow drain line, or in the
equipment-supplied drain pan, located at a point higher than
the primary drain line connection and below the overflow rim
of such pan."

Commentary

The operative word above is "or." The intent is simple: It needs to be made to work so the unit shuts off before it overflows. If that happens, the three listed choices are the Owner/Engineer/Contractor's option. The Code does not mandate two switches