Interpretation #7625

Published September 18, 2015

Original Request

Code Version
2014
Code
EXTBLDG
Code Description
Chapter
Section
602.2
Topic
Repairs to an existing building

Question

Is it the intent of 602.2 to allow the installation of materials which are similar in appearance, but are of different composition, for siding replacement and do those repairs only have to comply with the applicable code at the time that the building was originally erected?

Answer Published 09/18/2015 at 4:16 PM

Yes, 602.2 allows like material for alteration or repair,
this would apply to siding, the material would have to be
installed per its product approval and current code.

Commentary

Firstly, the reference to Section 606.2.1 in the "Comment" is irrelevant unless the siding is a structural element. Secondly, like materials is not defined and is not exactly the same as the material being replaced, the local official would be the one to determine if it is acceptable as a like material.