Interpretation #7614

Published September 16, 2015

Original Request

Code Version
2014
Code
ELECTRIC
Code Description
Chapter
Section
C405.2.2.3.1
Topic
Lighting control

Question

Is it the intent of this section to require the manual control function to adjust the lighting power in the same degree as the automatic control in Section C405.2.2.3.2?

Answer Published 09/16/2015 at 11:23 AM

No. The Code clearly states, "manual controls shall be
installed in daylight zones unless automatic controls are
installed..." A switch is a manual control. A switch is
what is necessary and sufficient under C405.2.2.3.1. The
Code is silent on any additional requirement pertaining to
manual controls' function.

Commentary

This particular requirement applies solely to the daylight zone zones which may not exceed 2500 sq. ft. The section does not apply to the general lighting system. There are numerous other provisions of this section of the code that must be considered as well.