Interpretation #7578
Published August 20, 2015
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 5
- Section
- 513.3
- Topic
- Smoke testing authority
Question
Does the local AHJ such as the Chief Mechanical Inspector have the authority to require "cold smoke" , such as smoke bombs, to use in testing of Smoke Control Systems, such as Pressurization method, Airflow design method and Exhaust method?
Answer Published 08/20/2015 at 10:23 AM
No.
Commentary
The use of smoke bombs can't be forced. What can be
enforced is the need to submit a test plan and to have the
AHJ approve the test plan. The test plan may or may not
include the use of smoke bombs, at the engineer of record's
option.