Interpretation #7578

Published August 20, 2015

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
513.3
Topic
Smoke testing authority

Question

Does the local AHJ such as the Chief Mechanical Inspector have the authority to require "cold smoke" , such as smoke bombs, to use in testing of Smoke Control Systems, such as Pressurization method, Airflow design method and Exhaust method?

Answer Published 08/20/2015 at 10:23 AM

No.

Commentary

The use of smoke bombs can't be forced. What can be enforced is the need to submit a test plan and to have the AHJ approve the test plan. The test plan may or may not include the use of smoke bombs, at the engineer of record's option.