Interpretation #7574

Published August 20, 2015

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
513.3
Topic
Use of smoke bombs

Question

In regards to Informal Interpretation Report Number 7540, which indicates " No, it is not the intent to use smoke bombs. ". If smoke is not to be used, how is the Fire Inspector able to determine that smoke has cleared in the allotted time of 13 minutes to see the exit sign from 20 feet away, per Fire Code criteria?

Answer Published 08/20/2015 at 10:23 AM

Ask the design engineer. It may not be the intent of the
Code to require smoke bombs, but smoke bombs can certainly
be used if the approved testing methodology employs them.

Commentary

As a note - Smoke bombs do not provide the same hot smoke a fire does. Even if the test was done with smoke bombs and passed, it would not necessarily mean it would perform the same in a real fire.