Interpretation #7565

Published November 13, 2015

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
R322.2.1
Topic
Freeboard

Question

Is it the intent of R322.2.1 to require a 1 foot free board when the established design flood elevation (DFE) is the base flood elevation (BFE)?

Answer Published 11/13/2015 at 12:18 PM

Yes. Required only when the structure is located in the
"floodway" because the designer shall use ASCE 24.

Yes. When the structure is in a "Coastal A Zone"


No. If the "otherwise legally designated" local design
flood elevation is already more than the published DFIRM BFE
+1'.

Sometimes. If the structure is in a "Flood Hazard Area" and
the design professional elects as an alternative design
provision to use ASCE 24 instead of the prescriptive
requirements of Section 322.

Commentary

None