Interpretation #7547

Published August 01, 2015

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R322
Topic
BFE and freeboard

Question

Is it the intent of R322 to require single family residences to be elevated 1 ft above the BFE as defined on the jurisdictions FIRM maps?

Answer Published 08/01/2015 at 2:47 PM

Yes, if it is in a floodway. 322.1 exception

states "Buildings or structures located in whole or

part in identified floodways shall be designed and

constructed in accordance with ASCE 24."

Commentary

The design is required to comply with ASCE 24 provided the structure is in an identified floodway. (s.R301.2.4, s.R322.1) However, the question indicates all SFRs and does not specify a flood zone category or that the structure is in a floodway. The additional 1 foot elevation may not always be required by the code except in Coastal A Zones. In Coastal A Zones, the lowest floor is required by the code to be elevated to or above the BFE plus one foot or to the design elevation, whichever is higher. In flood hazard areas not designated as Coastal A Zones, the floor is required to be elevated to or above the design flood elevation. Local flood ordinances may also require additional elevation.