Interpretation #7541

Published July 20, 2015

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
R302.1
Topic
Fire Separation Distance

Question

Please clarify; If our community of existing single family residences are built in a planned unit development and currently have 5' side yard setbacks, will our overhangs of 12" to 24" be required to be enclosed and fire rated?

Answer Published 07/20/2015 at 12:21 PM

Yes, for buildings permitted after midnight June 30, 2015.
(Midnight being the hour 12 a.m. between June 29 and June
30.) The 5th Edition changes the minimum fire separation
distance from 3 feet to less than 5 feet for
non-sprinklered buildings. In order to have a non-rated wall
the fire separation distance has to be equal to or less than
five feet for the wall and the projection. with a 5 feet
set-back the wall could be non-rated, but the projection
would have to be rated one hour on the underside.

Commentary

Requirements for new construction will not impact previously permitted/existing homes until such time as renovations/additions are undertaken that require compliance based upon the existing building code in affect at the time of renovation/addition.