Interpretation #7540
Published July 20, 2015
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 5
- Section
- 513.3
- Topic
- Testing of smoke exhast systems
Question
Is it the intent of FBC 2010 Mechanical 513.3 Special Inspection and Test Requirements, to require the use of smoke bombs / generators, creating smoke, for testing of the smoke control/ evacuation systems?
Answer Published 07/20/2015 at 12:20 PM
No, it is not the intent to use smoke bombs. The code does
not specify the method used for testing smoke control the
systems, it is the designers responsibility to include the
method of testing.
not specify the method used for testing smoke control the
systems, it is the designers responsibility to include the
method of testing.
Commentary
While the code does not specify how to do the test, cold
smoke is a poor method which does not accurately indicate
how the system will work under real time conditions.
A Special Inspector (FBC 909.18.8) is responsible to oversee
all phases of a smoke control system. He checks the system
for compliance to plans and rational analysis, during
erection of ductwork and prior to concealment, test for
leakage and record device locations. He is responsible to
review, inspect, test, and report integrity sealing
deficiencies as outlined in the projects specifications. The
Special Inspector is required by the code and hired by the
owner. Generally special inspection agencies for smoke
control have expertise in fire protection engineering,
mechanical engineering and certification as air balancers.
The Special Inspector has to be present, prior to occupancy
and after sufficient completion for the purposes of
pressure-difference testing, flow measurements, and
detection and control verification.
In the pressurization method, the primary means of
controlling smoke utilizes mechanical equipment, such as
AHUs, exhaust/supply fans, fire/smoke dampers, etc., to
provide a minimum positive-pressure differential relative
to adjacent spaces. A manometer is used to verify the
pressure differentials are achieved. Areas to be tested may
be between the floor of incident and the adjacent rooms or
if designed to the adjacent floors, between the stair
enclosure and the adjacent floor and/or vestibule without
exceeding a 30-lb door opening force. I have used smoke to
show velocity of the system and direction of flow.