Interpretation #7539

Published July 20, 2015

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
513.6
Topic
Smoke removal

Question

Is it the intent of FBC 2010 Mechanical 513.6, Pressurization method, to have the floor of fire origin, exhaust or remove smoke ? The last sentence of the Code section indicates " Maintenance of a tenable environment is not required in the smoke control zone of fire origin. ".

Answer Published 07/20/2015 at 12:19 PM

No, it is not the intent of this section to require exhaust.

Commentary

The intent is to prevent the spread of smoke to other floors or exit paths by keeping the smoke in the zone of origin through pressure "differences". This may result from exhausting the space lower than surrounding spaces or increasing pressures in surrounding spaces. If the space is exhausted at the same time surrounding areas are pressurized, it is easy to exceed the maximum allowable door opening/closing forces per 513.6.2. So long as that force is not exceeded, internal exhaust and external pressurization could be combined.