Interpretation #7535

Published August 03, 2015

Original Request

Code Version
2014
Code
MECHANIC
Code Description
Chapter
Section
507.16.1
Topic
Type II Hood capture system

Question

Is it the intent of this section to require a capture and containment test to be performed on a Type II hood system?

Answer Published 08/03/2015 at 8:16 AM

Yes

Commentary

507.16 states �the test shall verify the rate of exhaust airflow required by Section 507.13�. Section 507.13 covers type I and type II hoods